A Review of Some Representative Techniques for Controlling the Indoor Volatile Organic Compounds
Ehsanul Kabir ; Ki-Hyun Kim1), *
Department of Farm, Power & Machinery, Bangladesh Agricultural University, Mymensingh, Bangladesh
1)Department of Environment & Energy, Sejong University, Seoul 143-747, Korea

Correspondence to : *Tel: +82-2-3408-3233, Fax: +82-2-3408-4320, E-mail: khkim@sejong.ac.kr

Funding Information ▼

Abstract

Poor indoor air quality is now worldwide concern due to its adverse impacts on our health and environment. Moreover, these impacts carry a significant burden to the economy. Various technical approaches (e.g., biological, activated carbon fiber (ACF), photocatlytic oxidation (PCO), etc.) have gained popularity in controlling indoor volatile organic compounds (VOCs). This is because removing indoor VOC sources or increasing ventilation rates is often not feasible or economical. This review provides an overview of the various air purification technologies used widely to improve indoor air quality. Although most of these technologies are very useful to remove indoor VOCs, there is no single fully satisfactory method due to their diversity and presence at the low concentration. To achieve technical innovations and the development of specific testing protocols, one should possess a better knowledge on the mechanisms of substrate uptake at VOC concentrations.


Keywords: Volatile organic compounds (VOCs), Indoor air quality, Biological treatment, Activated carbon fiber (ACF), Photocatlytic oxidation (PCO)

1. INTRODUCTION

Indoor air quality (IAQ) remains a very important issue today because it can affect human life in many respects (such as health, comfort, satisfaction, and productivity). In the present world, majority of people spend most of their time in indoor environments, e.g., residences, public buildings, and offices (US EPA, 2002; Klepeis et al., 2001; Robinson and Nelson, 1995). With the improvement of living standard and innovation of construction technology, modern airtight buildings are equipped with air-conditioning systems and synthetic materials for decorating and remodeling purposes. The concentration level of indoor air pollutants can increase several hundred times higher than that of outdoor ones (Orwell et al., 2004; Fisk, 2000; Brown, 1997). The prevalence of volatile organic compounds (VOCs) (e.g., formaldehyde, benzene, toluene, xylene, etc.) in indoor environment may trigger immediate or persistent harm to human health (Wolkoff, 2003). The phenomena of sick building syndrome (SBS), building related illness (BRI), or multiple chemical sensitivity (MCS) have been reported frequently in recent years (Liu, 2007; Runeson et al., 2006).

There are a variety of approaches for controlling VOCs in indoor environments such as source control, ventilation, and air cleaning (Lu et al., 2010). Ventilation is commonly the most efficient method but can be disadvantageous for requiring more energy consumption (Khoukhi et al., 2007). At present, air purification remains to be one of the most promising air-cleaning methods to involve diverse control techniques, e.g., adsorption by activated carbon, photocatalytic oxidation (PCO), biological treatment (biofiltration, bioscrubber, vegetation approach, etc.), catalytic oxidation, adsorption, ionization methods (plasma, photocataytic oxidation, etc.), and other miscellanea ous ones (Ao and Lee, 2003; Shen and Ku, 2002). This paper presents a critical review on the potential and limitation of the three air purification technologies (i.e., biological treatment, ACF, and PCO) in light of the widest applicabiluity indoor air quality management.


2. VOCS AND INDOOR AIR QUALITY

Hundreds of VOCs with diverse physical, chemical, and biological properties can be found simultaneously in indoor air. Indoor VOC concentrations are generally higher than outdoor concentrations because VOCs can be released from human activities and a wide variety of indoor sources such as floorings, linoleum, carpets, paints, surface coatings, furniture, etc (Yu and Crump, 1998). These compounds exhibit very large variations in concentration as the composition of the mixture released from many sources gradually varies through time. However, there are also certain substances of which release depends on punctual human activities or even human breathing (Miekisch et al., 2004; Phillips, 1997; Ekberg, 1994). Indoor VOC concentrations can be controlled further by such variables as the total space volume, the pollutant production and removal rates, air exchange rate with the outside atmosphere, and the outdoor VOC concentrations (Salthammer, 1997).

Furniture coatings were found to release as many as 150 diffent VOCs (mainly aliphatic and aromatic aldehydes, aromatic hydrocarbons, ketones, etc.) (Salthammer, 1997). As several hundreds contaminants can be found simultaneously, they can result in significant rise in total volatile organic compound (TVOC) levels (Yu and Crump, 1998; Kostiainen, 1995). The effect of such rise on human health hazard is not easy to evaluate, as this generic parameter does not reflect the individual differences in toxicities between indoor air VOCs. However, symptoms (such as headache, drowsiness, fatigue, and confusion) have been recorded in subjects exposed to 22 VOCs (Hudnell et al., 1992). In addition, many harmless VOCs can react with oxidants such as ozone, producing highly reactive compounds that can be more harmful than their precursors (Sundell, 2004; Wolkoff and Nielsen, 2001; Wolkoff et al., 1997). Commonly available VOCs in indoor environment and their sources are listed in Table 1.

Table 1. 
Commonly available VOCs in indoor environment and their sources (Tucker, 2001).
Order Chemical Source
1 Acetone Paint, coatings, finishers, paint remover, thinner, caulking
2 Aliphatic hydrocarbons (octane, decane, undecane hexane, isodecane, mixtures, etc.) Paint, adhesive, gasoline, combustion sources, liquid process photocopier, carpet, linoleum, caulking compound
3 Aromatic hydrocarbons (toluene, xylenes, ethylbenzene, benzene) Combustion sources, paint, adhesive, gasoline, linoleum, wall coating
4 Chlorinated solvents (dichloromethane or methylene chloride, trichloroethane) Upholstery and carpet cleaner or protector, paint, paint remover, lacquers, solvents, correction fluid, dry-cleaned clothes
5 n-Butyl acetate Acoustic ceiling tile, linoleum, caulking compound
6 Dichlorobenzene Carpet, moth crystals, air fresheners
7 4-Phenylcyclohexene (4-PC) Carpet, paint
8 Terpenes (limonene, a-pinene) Deodorizers, cleaning agents, polishes, fabrics, fabric softener, cigarettes


3. INDOOR AIR TREATMENT
3. 1 Biological Treatment

Most of the biological treatments for indoor pollutants primarily focused on botanical purifiers. In some previous studies, it was found that ornamental indoor plants have the ability to remove harmful VOCs from indoor air (Claudio, 2011; Yang et al., 2009; Tarran et al., 2007; Orwell et al., 2006; Wood et al., 2003). Previous studies revealed that indoor plants could reduce stress and boost performance levels at work because they could soak up harmful air pollutants which may otherwise cause drowsiness, fatigue, and heavy-head feeling (Burchett et al., 2008; Fjeld, 2002). In Table 2 a list of plants suitable for removing individual pollutants is listed with their potential for individual VOC.

Table 2. 
VOC removal efficiency by indoor plants over 6 h duration (Yang et al., 2009).
Order Plant VOC removal efficiency (μg m-3 m-2 h-1)
Benzene Toluene Octane Trichloroethylene (TCE) α-Pinene Total
1 Hemigraphis alternata 5.54±0.29 9.63±0.94 5.58±0.68 11.1±0.99 12.2±1.61 44.0±2.98
2 Hedera helix 3.63±0.33 8.25±0.64 5.10±0.49 8.07±0.77 13.3±0.95 38.3±3.17
3 Tradescantia pallida 3.86±0.58 9.10±1.12 2.76±1.08 7.95±1.20 10.5±1.78 34.1±5.52
4 Asparagus densiflorus 2.65±0.24 7.44±0.28 3.76±0.64 6.69±0.49 11.4±0.78 31.9±2.40
5 Hoya carnosa 2.21±0.21 5.81±0.67 3.80±0.62 5.79±0.75 8.48±1.17 26.1±3.40
6 Ficus benjamina 1.66±0.07 5.06±0.19 3.98±0.19 4.74±0.15 4.68±0.40 24.1±0.86
7 Polyscias fruticosa 1.53±0.08 4.29±0.04 3.43±0.08 3.98±0.16 8.30±0.12 21.5±0.42
8 Frttotia argroneuro 2.74±0.28 5.09±0.23 1.77±0.25 6.15±0.36 4.30±0.39 20.1±1.46

In a pioneer study supported by the NASA, Wolverton and coauthors (1984) demonstrated the potential of plants (and their rizosphere) to remove indoor VOCs in sealed chamber. In their earliest study, these authors found that several plants could remove formaldehyde at 15,500-37,500 ppb, benzene and trichloroethylene at 102-686 ppb in 24 h (Wolverton et al., 1989; Wolverton et al., 1984). Through their research, Wolverton and Wolverton (1993) also found that the air-cleaning capacity of houseplants can be improved exponentially by increasing air circulation to the roots of the plants, where symbiotic microorganisms can help make the bioavailable substances culled. Orwell et al. (2004) investigated the potential of indoor plants for removing benzene in sealed chamber (0.216m3) and found that microorganisms of the plant rizosphere were mainly responsible for its removal (12-25 ppm d-1). These results were obtained at high initial benzene concentrations (25-51 ppm). They observed that benzene removal rate increased linearly with the dosed concentration, suggesting that the system should be inefficient under typical indoor air conditions. The same team in another experiment demonstrated that plants significantly reduced toluene and xylene at indoor air concentrations of 203-235 ppb (Orwell et al., 2006). Tarran et al. (2007) found that indoor-plants could reliably reduce TVOC by 75% in their laboratory studies (with nine species) and field studies (in 60 offices). In a previous study, it was observed that three plants in a real office of average area 13m2 (volume 32.5m3) were more than enough to reduce TVOC by up to over 75% with or without air-conditioning (Wood et al., 2006). Nevertheless, studies have demonstrated that it was the microorganisms at the root-zone of the plants which were the primary removal agents of the VOCs (Orwell et al., 2006). Therefore, if the polluted air is introduced into a plant root system and degraded by the microorganisms, the removal capacity of the plant can be improved further than the potted plant with leaf effect only. Studies also showed that plants grown in hydroculture were more effective in removing VOCs than soil-grown plants, primarily due to increased air flow to root microbes (Burchett, 2005). Hydroculture also has many other added benefits such as reducing the incidence of mold and mildew as the surface remains dry (Burchett, 2005).

Many parameters such as the interfacial areas, the moisture content, and the hydrophobicity of the selected biomass can influence pollutant removal in biological purifiers. Sandhu (2007) suggested that bacteria growing on plant leaves could also contribute to VOC biodegradation. Direct pollutant accumulation or degradation by plants has however been demonstrated to occur during phytoremediation of contaminated soils (Newman and Reynolds, 2004). The ability of plant leaves to directly take up and remove pollutants for air treatment is still however open for debate (Schäffner et al., 2002; Schmitz et al., 2000; Wolverton et al., 1984).

Just placing a few plants inside a building will not solve a serious IAQ problem, while ventilation alone cannot take such role either (Girman et al., 2009). Several factors should be considered concurrently to optimize the use of plants for the improvement of indoor quality. Note that the output of chamber studies can be meaningful, if concentrations selected for such tests can actually represent those present in actual indoor environments. Moreover, chamber study results should be reported as mass of pollutant removed per hour per plant mass to facilitate direct comparisons with other removal methods. The schematic of a sample chamber test set-up is shown in Fig. 1.


Fig. 1. 
Schematic diagram of the chamber test setup by indoor plants: (A) top-view and (B) side-view.

3. 2 Activated Carbon Fiber (ACF)

Adsorption process is one of the most efficient and safest processes to remove VOCs from indoor air (Bastani et al., 2010; Benne and Griffith, 2009). Activated carbon fiber (ACF) filter is a promising technology for removing VOCs from indoor air because of its regenerative properties (Huang et al., 2010; Yao et al., 2009a; Haghighat et al., 2008; Das et al., 2004). ACF is generally made from rayon, polyacrylonitrile (PAN), or phenolic resin (Huang et al., 2010). The fibers are woven into a fabric and then activated in steam or CO2 at high temperatures (e.g., 800°C). The narrow pore size contributes to the large adsorption capacity of ACF. ACF also has large surface areas, which range from 1000 to 2400m2g-1, with a typical value of 1800 m2g-1 (Huang et al., 2010; Lorimier et al., 2005; Das et al., 2004). ACF does not contain impurities that can catalyze oxidative reactions and lead to decomposition of the adsorbate within the adsorbent (Das et al., 2004). Accordingly to the previous studies, ACF filters are very good VOC adsorbents, to show improved performance relative to granular activated carbon, zeolites, and silica gel under identical operation conditions (Huang et al., 2010; Das et al., 2004; Liu, 1992).

To utilize the ACF filter more efficiently, it can require regeneration step in which the adsorbed VOCs must be periodically desorbed from the filter (and exhausted outdoors). There are three different regeneration methods for the filters ((i) using outdoor air under ambient conditions, (ii) with humidified air, and (iii) with heated air). Among these options, the best performance was achieved by regenerating it for 15 minutes once every 12 hours by employing heated air up to 150°C (Dombrowski et al., 2004). The air flow during regeneration was maintained as only 1 percent of the total airflow during the 12-hour period of air cleaning (Dombrowski et al., 2004). Hence, only a very small amount of air needs to be heated, regarding the small amount of energy for regeneration.

Although activated carbon filters can remove a broad range of VOCs from indoor air, their capacity to adsorb formaldehyde is relatively low (Fisk, 2007). Huang et al. (2010) studied the performance of ACF with a mixture of VOC (a molecular weight of 30 to 156 and boiling point of -21 to 196°C). The time-averaged removal efficiency of all except formaldehyde was above 70 percent, while that of formaldehyde was approximately 20 percent. However, using a double layer, ACF cloth, Huang et al. (2010) found such efficiency can be raised to 40 percent, while those of others also exceeded 90 percent.

ACF media has a long adsorption life time and can be used effectively to remove indoor VOCs with periodic regeneration (Ramirez et al., 2005). The isotherm data obtained for the ACF showed that it took about 100 hours to fully saturate the ACF media with realistic concentrations of indoor VOCs (Sidheswaran et al., 2011). Yao et al. (2009b) suggested that short periods of DC electrical heating (150 to 200°C) of the carbon fibers was a promising option for periodically regenerating ACF. As an alternative to DC heating of the ACF media, regeneration might be accomplished by passing heated air through the ACF media (Sidheswaran et al., 2011). During the heating period, air is supplied through the ACF at a low flow rate to be exhausted outdoors. This process can also re-transport the desorbed VOCs vented from the building. As an alternative to DC heating (of the ACF media), regeneration can be accomplished by passing heated air through the ACF media (Ramirez et al., 2005). Moreover, results from periodic adsorption and desorption experiments showed that the ACF media should be easily regenerated after a 12 or 24 hour period of air cleaning (Sidheswaran et al., 2011).

Modeling indicates that the combination of ACF air cleaning and a 50 percent reduction in ventilation can decrease indoor concentrations of VOCs by 60 to 80 percent, while reducing formaldehyde by 12 to 40 percent (Yao et al., 2009b). Thus, the system can suppress exposures to VOCs and formaldehyde, while simultaneously reducing the ventilation (up to half) to save energy. However, it is essential to optimize parameters such as duration and frequency of regeneration cycles, the air flow rate, and temperature. The ACF system must be energy efficient compared to the traditional ventilation process, while still capable of providing sufficient regeneration during periods of building occupancy (Sidheswaran et al., 2011). Nevertheles, most previous studies of ACF to remove indoor VOCs were limited to high concentrations of VOCs(ppm) with a few limited target compounds (Benne and Griffith, 2009). However, to allow a reduction in ventilation rates, an air cleaning system needs to be effective in removing a broad spectrum of VOCs that are present simultaneously in the indoor air at low ppb-level concentrations. Table 3 shows the percent removal efficiency of different VOCs and the corresponding air cleaning ration (Ri) values for different conditions. Here, i is defined as the ratio of the indoor VOC concentration with an air handling unit with the ACF filter installed in the system to the indoor VOC concentration with an air handling unit without the ACF filter. It was observed that in both the low (0.4 h-1) and high (0.6 h-1) ventilation rates, the system equipped with heated ACF filter bed performed better than the system without it. It was also observed that cases in which ACF was regenerated by heating have lower Ri values than the corresponding cases in which ACF was regenerated with unheated outdoor air. This suggests that the heated regeneration method should improve ACF VOC-removal performance compared to the unheated outdoor air regeneration method. The schematic diagram of the experimental set-up used for the regeneration of ACF is shown in Fig. 2. The regeneration of ACF was carried out by electrical heating and nitrogen flow. A complete regeneration of ACF typically requires temperature of ~150°C and regeneration time of 60-75 min. The temperature is monitored by a thermocouple fixed at the surface of the ACF sample. The concentration of the exit gas from the reactor can be measured with the help of a gas chromatography (GC) using flame ionization detector (FID).

Table 3. 
Percent removal efficiency and air cleaning effectiveness ratio for ACF with different regeneration techniques (VOC source emission rate=6.4 ppb h-1 for each compound).
VOCs Conditions Percent removal efficiency VOC cleaning ratio (Ri) Reference
Benzene Heated outdoor air regeneration and outdoor air ventilation rate of 0.4 h-1 60 0.26 Sidheswaran et al., 2012
1-Butanol 71 0.23 Yao et al., 2009b
Toluene 65 0.24 Lorimier et al., 2005
o-Xylene 73 0.22 Yao et al., 2009b
Limonene 73 0.22 Sidheswaran et al., 2012
Undecane 76 0.21 Sidheswaran et al., 2012
Formaldehyde 24 0.56 Yao et al., 2009b
Benzene Unheated outdoor air regeneration and outdoor air ventilation rate of 0.4 h-1 46 0.33 Sidheswaran et al., 2012
1-Butanol 53 0.29 Yao et al., 2009b
Toluene 60 0.26 Lorimier et al., 2005
o-Xylene 56 0.28 Yao et al., 2009b
Limonene 54 0.29 Sidheswaran et al., 2012
Undecane 54 0.29 Sidheswaran et al., 2012
Formaldehyde 16 0.72 Yao et al., 2009b
Benzene Heated outdoor air regeneration and outdoor air ventilation rate of 0.6 h-1 60 0.36 Sidheswaran et al., 2012
1-Butanol 71 0.31 Yao et al., 2009b
Toluene 65 0.33 Lorimier et al., 2005
o-Xylene 73 0.30 Yao et al., 2009b
Limonene 73 0.30 Sidheswaran et al., 2012
Undecane 76 0.29 Sidheswaran et al., 2012
Formaldehyde 24 0.71 Yao et al., 2009b
Benzene Unheated outdoor air regeneration and outdoor air ventilation rate of 0.6 h-1 46 0.44 Sidheswaran et al., 2012
1-Butanol 53 0.40 Yao et al., 2009b
Toluene 60 0.36 Lorimier et al., 2005
o-Xylene 56 0.38 Yao et al., 2009b
Limonene 54 0.39 Sidheswaran et al., 2012
Undecane 54 0.39 Sidheswaran et al., 2012
Formaldehyde 16 0.88 Yao et al., 2009b


Fig. 2. 
Schematic diagram of the experimental set-up for the regeneration of ACF (1. N2 gas cylinder, 2. Mass flow controller, 3. Isolation valve, 4. SS shell, 5. ACF wrapped over Teflon tube, 6. Isolation bypass valve, 7. DC generator, 8. Voltmeter, 9. Ammeter, 10. Thermocouple with PID controller, 11. GC with FID).

3. 3 Photocatalytic Oxidation (PCO)

Photocatlytic oxidation (PCO) is a promising technology for the remediation of organic pollutants which has been under development for a number of years (Tompkins et al., 2005; Zhao and Yang, 2003). It is a cost-effective technology for VOCs removal compared with adsorption, biofiltration, or thermal catalysis (Dvoranova et al., 2002; Kim et al., 2002). PCO process harnesses radiant energy from natural (or artificial) light sources with heterogeneous catalyst to degrade the organic pollutants into their mineral components (Li et al., 2005a; Ao et al., 2004; Hoffmann, 1995). Titanium dioxide (TiO2) is the most widely used catalyst for the photocatalytic reaction (Wang et al., 2007). Other semiconductors (such as ZnO, ZnS, CdS, Fe2O3, and SnO2) are also commonly used catalysts (Wang et al., 2007). The PCO process creates hydroxyl radicals and super-oxide ions, which are highly reactive electrons (Pichat et al., 2000). These highly reactive electrons aggressively combine with the air pollutants (e.g., VOCs). Once bound together, the chemical reaction takes place between the super-charged ion and the pollutant to effectively oxidize (or burn) the pollutant. This breaks the pollutants down into harmless components (carbon dioxide and water molecules), making the air more purified (Hodgson et al., 2007).

Wang et al. (2007) supplied VOCs contaminated air over a titanium dioxide (TiO2) catalyst at room temperature, while illuminating with a black lamp. These authors found that over 95% of the VOCs were converted to carbon dioxide and water. At 70°C, the reaction rates were three to four times faster than at room temperature. They also revealed that a platinum-doped (Pt/TiO2) catalyst could achieve even higher reaction rates without producing any detectable carbon monoxide (Wang et al., 2007). Performance of the Pt/TiO2 catalyst was improved further with increasing temperature with both thermal and photocatalytic effects to contribute to the compound destruction (Wang et al., 2007). The best performance was obtained at 150°C which was the highest temperature selected for their testing (Wang et al., 2007). Addition of ozone to the air stream also increased the process efficiency, but the use of ozone can raise safety and cost issues. Stevens et al. (1998) reported the operational characteristics of four PCO reactor designs using P25 TiO2 for the oxidative destruction of formaldehyde, acetaldehyde, and acetone. Their result showed that photodegradation of acetaldehyde was lower than that for formaldehyde and acetone. PCO of the formaldehyde and acetone was nearly 100% for all reactor designs (Stevens et al., 1998). Cao et al. (2000) investigated the nanoscale TiO2 catalysts for the photocatalytic oxidation of toluene. They found that the nanoscale TiO2 samples were highly active for the photodegradation of toluene. However, the use of platinum loaded on TiO2 could facilitate the removal of poisonous intermediates from the deactivated TiO2 surface, while resulting in lower oxidation rates of toluene (Cao et al., 2000). Pichat et al. (2000) employed a TiO2 coated fiber glass mesh composed of anatase TiO2 and SiO2 for photocatalytic oxidation of benzene, toluene, and xylenes (BTX) in indoor air. According to their study the average concentrations of BTX were indeed reduced by a factor of 2-3 in an ordinary non-airtight room.

Li et al. (2005b) reported that the photocatalytic efficiency of the TiO2 catalysts with the lanthanide ion doping can exhibit remarkably enhanced removal efficiency for BTEX. The 1.2% Ln3+-TiO2 catalysts achieved the highest photocatalytic activity. The enhanced photo degradation of BTEX is possibly due to the improved adsorption ability and the enhanced electronhole pairs separation due to the presence of Ti3+on the surface of Ln3+-TiO2 catalysts and the electron transfer between the conduction band/defect level and lanthanide crystal field state (Li et al., 2005b). Shiraishi et al. (2005) developed a high-performance photocatalytic reactor with a parallel array of nine light sources for photocatalytic decomposition. These authors found that this photocatalytic reactor can rapidly decompose HCHO toward zero concentration. It was recognized that at high humidity levels, water vapor competed with TiO2 for adsorption sites which decreased the rate of PCO.

To improve this situation, Ao and Lee (2003) developed an activated carbon (AC) filter immobilised with TiO2 (TiO2/AC). The results indicated that the removal efficiency of TiO2/AC was seven times higher than TiO2 under high humidity levels. Shen and Ku (2002) found that the addition of ozone into the TiO2/UV/TCE system with 254 or 365 nm UV lamps reduced the removal of TCE, possibly because excessive ozone molecules could scavenge hydroxylradicals produced from the excitation of TiO2 by UV radiation. Kirchnerova et al. (2005) explored the photocatalytic activities of two commercial TiO2 catalysts, Degussa P25 and Hombicat UV100, for n-butanol decomposition under visible light. They found that Degussa P25 was more active than Hombicat UV100. One new approach to produce visible-light activated TiO2 photocatalysts is by doping with anions such as N3-, C4-, S4- or halides (F-, Cl-, Br-, and I-) (Belver et al., 2006). It was suggested that these species substitute the oxygen lattice on TiO2 and lead to a band gap narrowing which may ultimately lead to high visible absorption.

Yu et al. (2009) found that only the surface area of the reactor influenced the PCO rate sensitively, while the UV light had a better PCO effect than that of visible light. Hence, the consumption condition of the UV light in indoor will be an important issue of further studies. Yu and Brouwers (2009) conducted photocatalytic oxidation experiments at room temperature under visible light and demonstrated its convenience for the indoor air purification. Besides the photocatalyst, no other materials are required for the degradation of indoor air pollutants. However, hexamethyldisilazane cannot be treated effectively using PCO techniques. Because of silicon containing reaction products, the catalyst is deactivated minutes after hexamethyldisilazan contact (Wang et al., 2007). The catalyst can hence be reactivated partially by flushing with water or other solvents. Nonetheless, the speed with which deactivation takes place renders any sort of regeneration process impractical (Wang et al., 2007).

Table 4 summarizes the results on various photocatalytic oxidations for indoor VOCs. The schematic diagram of the PCO setup for indoor air assessment is also plotted in Fig. 3. This experimental setup is composed of the reactor, gas supply, analyzer, parameters controller, etc. A known amount of photocatalyst (e.g., P25 TiO2) is coated onto the inner wall of the glass tube. Exact photon output from the lamp is measured periodically with an ultraviolet (UV) spectrometer. The photo reactor can then be incorporated into a test system that allows researchers to vary flow rate, VOC air concentration, humidity, and temperature.

Table 4. 
Comparison of catalyst system used for VOCs degradation under UV-light.
Catalyst VOCs λ (nm) Initial concentration (ppb) Conversion (%) Reference
TiO2 (5%) Formaldehyde 356 15 80 Stevens et al., 1998
TiO2 (5%) Acetaldehyde 356 15 60 Stevens et al., 1998
TiO2 (5%) Acetone 356 15 100 Stevens et al., 1998
TiO2 (6.8%) Benzene 365 15 30 Pichat et al., 2000
TiO2 (6.8%) m-Xylene 365 40 50 Pichat et al., 2000
TiO2 (6.8%) p-Xylene 365 60 55 Pichat et al., 2000
TiO2 (6.8%) o-Xylene 365 20 50 Pichat et al., 2000
TiO2 (20%) Benzene 352 93 100 Jo et al., 2000
TiO2 (20%) m-Xylene 352 78 100 Jo et al., 2000
TiO2 (20%) p-Xylene 352 78 100 Jo et al., 2000
TiO2 (20%) o-Xylene 352 45 100 Jo et al., 2000
TiO2 (20%) Ethyl benzene 352 21 100 Jo et al., 2000
TiO2 (5%) Benzene 365 20 70 Ao and Lee, 2003
TiO2 (5%)/AC Benzene 365 20 80 Ao and Lee, 2003
TiO2 (5%) Toluene 365 20 88 Ao and Lee, 2003
TiO2 (5%)/AC Toluene 365 20 88 Ao and Lee, 2003
TiO2 (1%) Benzene 355 88 5 Strini et al., 2005
TiO2 (1%) Toluene 355 80 24 Strini et al., 2005
TiO2 (1%) Ethyl benzene 355 65 48 Strini et al., 2005
TiO2 (1%) o-Xylene 355 60 54 Strini et al., 2005
TiO2 (5%) Benzene 365 23 4 Li et al., 2000b
La (1.2%)/TiO2 (5%) Benzene 365 23 30 Li et al., 2000b
Nd (1.2%)/TiO2 (5%) Benzene 365 23 22 Li et al., 2000b


Fig. 3. 
Schematic diagram of the photo catalytic oxidation setup.


4. CONCLUSIONS

This review presents an overview of the various technical approaches (e.g., biological, ACF, and PCO) currently available for indoor air treatment. Nonetheless, there is yet no single fully satisfactory method for VOC removal from indoor air due to the difficulties linked to the very low concentration, diversity, and variability of VOCs in the indoor environment. Although the above mentioned methods have shown certain potential for the removal of VOC, the specific characteristics of indoor air pollutants and the indoor environment can yield numerous challenges. In particular, new methods must be developed to inoculate, express, and maintain a suitable and diverse catabolic ability under the conditions of trace substrate concentration. In addition, the methods for the treatment of indoor air must be able to purify a large amount of air in spatially confined environments with minimal nuisances. This requires technical innovations, the development of specific testing protocols, and a better understanding of the activities and the mechanisms of VOC uptake by different substrates.


Acknowledgments

This study was supported by a National Research Foundation of Korea (NRF) grant funded by the Ministry of Education, Science and Technology (MEST) (No. 2010-0007876).


References
1. Ao, C.H., Lee, S.C., (2003), Enhancement effect of TiO2 immobilized on activated carbon filter for the photodegradation of pollutants at typical indoor air level, Applied Catalysis B: Environmental, 44, p191-205.
2. Ao, C.H., Lee, S.C., (2004), Combination effect of activated carbon with TiO2 for the photodegradation of binary pollutants at typical indoor air level, Journal of Photochemistry and Photobiology A: Chemistry, 161, p131-140.
3. Bastani, A., Lee, C.-S., Haghighat, F., Flaherty, C., Lakdawala, N., (2010), Assessing the performance of air cleaning devices e A full-scale test method, Building and Environment, 45, p143-149.
4. Belver, C., Bellod, R., Fuerte, A., Fernandez-Garcia, M., (2006), Nitrogen-containing TiO2 photocatalysts: Part 1. Synthesis and solid characterization, Applied Catalysis B: Environmental, 65, p301-308.
5. Benne, K., Griffith, B., (2009), Assessment of the energy impacts of outside air in the commercial sector, NREL/TP-550-41955, Golden, CO, National Renewable Energy Laboratory.
6. Brown, S.K., (1997), Volatile organic compounds in indoor air: sources and control, Chemistry in Australia, 64, p10-13.
7. Burchett, M.D., (2005), Improving Indoor Environmental Quality Through the Use of Indoor Potted Plants, Final Report to Horticulture Australia Ltd, Sydney.
8. Burchett, M.D., Torpy, F., Tarran, J., (2008), Interior plants for sustainable facility ecology and workplace productivity, Proceedings of Ideaction’08-Enabling Sustainable Communities, Qld.
9. Cao, L.X., Gao, Z., Suib, S.L., Obee, T.N., Hay, S.O., Freihaut, J.D., (2000), Photocatalytic oxidation of toluene on nanoscale TiO2 catalysts: studies of deactivation and regeneration, Journal of Catalysis, 196, p253-261.
10. Claudio, L., (2011), Planting Healthier Indoor Air, Environ Health Perspect.
11. Das, D., Gaur, V., Verma, N., (2004), Removal of volatile organic compound by activated carbon fiber, Carbon, 42, p2949-2962.
12. Dombrowski, K.D., Lehmann, C.M.B., Sullivan, P.D., Ramirez, D., Rood, M.J., Hay, K.J., (2004), Organic vapor recovery and energy efficiency during electric regeneration of an activated carbon fiber cloth adsorber, Journal of Environmental Engineering, 130(3), p268-275.
13. Dvoranova, D., Brezova, V., Mazur, M., Malati, M.A., (2002), Investigations of metal-doped titanium dioxide photocatalysts, Applied Catalysis B: Environmental, 37, p91-105.
14. Ekberg, L.A., (1994), Volatile organic compounds in office buildings, Atmospheric Environment, 28, p3571-3575.
15. Fisk, J.W., (2000), Review of health and productivity gains from better IEQ, In Proceedings of Health Buildings, August 6-10, SIY Indoor Air Information, Oy, Helsinki.
16. Fisk, W.J., (2007), Can sorbent-based gas phase air cleaning for VOCs substitute for ventilation in commercial buildings?, In Proceedings of the IAQ 2007 Healthy and Sustainable Buildings, Atlanta: ASHRAE.
17. Fjeld, T., (2002), The effects of plants and artificial daylight on the well-being and health of office workers, school children and health-care personnel, Proceedings of International Plants for People Symposium, Floriade, Amsterdam, NL.
18. Girman, J., Phillips, T., Levin, H., (2009), Critical review: how well do house plants perform as indoor air cleaners?, Proceedings of Healthy Buildings, 23, p667-672.
19. Guieysse, B., Hort, C., Platel, V., Munoz, R., Ondarts, M., Revah, S., (2008), Biological treatment of indoor air for VOC removal: Potential and challenges, Biotechnology Advances, 26, p398-410.
20. Haghighat, F., Lee, C.-S., Pant, B., Bolourani, G., Lakdawala, N., Bastani, A., (2008), Evaluation of various activated carbons for air cleaning towards design of immune and sustainable buildings, Atmospheric Environment, 42, p8176-8184.
21. Hodgson, A.T., Destaillats, H., Sullivan, D.P., Fisk, W.J., (2007), Performance of ultraviolet photocatalytic oxidation for indoor air cleaning applications, Indoor Air, 17, p305-316.
22. Hoffmann, M.R., Martin, S.T., Choi, W., Bahnemann, D.W., (1995), Environmental applicationof semiconductor photocatalysis, Chemistry Reviews, 95, p69-96.
23. Huang, Y.C., Luo, C.-H., Yang, S., Lin, Y.-C., Chuang, C.-Y., (2010), Improved removal of indoor volatile organic compounds by activated carbon fiber filters calcined with copper oxide catalyst, CLEAN-Soil, Air, Water, 38(11), p993-997.
24. Hudnell, H.K., Otto, D.A., House, D.E., Mølhave, L., (1992), Exposure of humans to a volatile organic mixture II. Sensory, Archives of Environmental Health, 47, p31-38.
25. Jo, W.K., Park, J.H., Chun, H.D., (2002), Photocatalytic destruction of VOCs for in-vehicle air cleaning, Journal of Photochemistry and Photobiology A: Chemistry, 148, p109-119.
26. Khoukhi, M., Yoshino, H., Liu, J., (2007), The effect of the wind speed velocity on the stack pressure in mediumrise buildings in cold region of China, Building and Environment, 42, p1081-1088.
27. Kim, S.B., Hong, S.C., (2002), Kinetic study for photocatalytic degradation of volatile organic compounds in air using thin film TiO2 photocatlyst, Applied Catalysis B: Environmental, 35, p305-315.
28. Kirchnerova, J., Cohen, M.L.H., Guy, C., Klvana, D., (2005), Photocatalytic oxidation of nbutanol under fluorescent visible light lamp over commercial TiO2 (Hombicat UV100 and Degussa P25), Applied Catalysis A: General, 282, p321-332.
29. Klepeis, N.E., Nelson, W.C., Ott, W.R., Robinson, J.P., Tsang, A.M., Switzer, P., Behar, J.V., Hern, S.C., Engelmann, W.H., (2001), The national human activity pattern survey (NHAPS): a resource for assessing exposure to environmental pollutants, Journal of Exposure Analysis and Environmental Epidemiology, 11, p231-252.
30. Kostiainen, R., (1995), Volatile organic compounds in the indoor air of normal and sick houses, Atmospheric Environment, 29, p693-702.
31. Li, D., Haneda, H., Hishita, S., Ohashi, N., (2005a), Visible-light-driven nitrogen-doped TiO2 photocatalysts: effect of nitrogen precursors on their photocatalysis for decomposition of gas-phase organic pollutants, Materials Science and Engineering: B, 117, p67-75.
32. Li, F.B., Li, X.Z., Ao, C.H., Lee, S.C., Hou, M.F., (2005b), Enhanced photocatalytic degradation of VOCs using Ln3+-TiO2 catalysts for indoor air purification, Chemosphere, 59, p787-800.
33. Liu, R.T., (1992), An in-situ regenerative adsorber for the control of indoor VOCs activated carbon fibers, Proceedings of IAQ’92, Atlanta: ASHRAE 257-261.
34. Liu, X., (2007), Identification of appropriate CFD models for simulating aerosol particle and droplet indoor transport, Indoor and Built Environment, 16, p322-330.
35. Lorimier, C., Subrenat, A., Le-Coq, L., Le-Cloirec, P., (2005), Adsorption of toluene onto activated carbon fibre cloths and felts: application to indoor air treatment, Environmental Technology, 26(11), p1217-1230.
36. Lu, Y., Liu, J., Lu, B., Jiang, A., Wan, C., (2010), Study on the removal of indoor VOCs using biotechnology, Journal Hazardous Materials, 182, p204-209.
37. Miekisch, W., Schubert, J.K., Noeldge-Schomburg, G.F.E., (2004), Diagnostic potential of breath analysis-focus on volatile organic compounds, Clinica Chimica Acta, 347, p25-39.
38. Mo, J., Zhang, Y., Xu, Q., Lamson, J.J., Zh, R., (2009), Photocatalytic purification of volatile organic compounds in indoor air: A literature review, Atmospheric Environment, 43, p2229-2246.
39. Newman, L.A., Reynolds, C.M., (2004), Phytodegradation of organic compounds, Current Opinion in Biotechnology, 15, p225-230.
40. Orwell, L.R., Wood, L.R., Tarran, J., Torpy, F., Burchett, D.M., (2004), Removal of benzene by the indoor plant/substrate microorganism and implications for air quality, Water, Air, and Soil Pollution, 157, p193-207.
41. Orwell, R., Wood, R., Burchett, M., Tarran, J., Torpy, F., (2006), The potted-plant microcosm substantially reduces indoor air VOC pollution: II. Laboratory study, Water, Air, and Soil Pollution, 177, p59-80.
42. Phillips, M., (1997), Method for the collection and assay of volatile organic compounds in breath, Analytical Biochemistry, 247, p272-278.
43. Pichat, P., Disdier, J., Hoang-Van, C., Mas, D., Goutailler, G., Gaysse, C., (2000), Purification/deodorization of indoor air and gaseous effluents by TiO2 photocatalysis, Catalysis Today, 63, p363-369.
44. Ramirez, D., Qi, S., Rood, M.J., (2005), Equilibrium and heat of adsorption for organic vapors and activated carbons, Environmental Science and Technology, 39, p5864-5871.
45. Robinson, J., Nelson, W.C., (1995), The National Human Activity Pattern Survey Data Base, The National Human Activity Pattern Survey Data Base, Research Triangle Park, NC.
46. Runeson, R., Wahlstedt, K., Wieslander, G., Norback, D., (2006), Personal and psychosocial factors and symptoms compatible with sick building syndrome in the Swedish workforce, Indoor Air, 16, p445-453.
47. Salthammer, T., (1997), Emission of volatile organic compounds from furniture coatings, Indoor Air, 7, p189-197.
48. Sandhu, A., Halverson, L.J., Beattie, G.A., (2007), Bacterial degradation of airborne phenol in the phyllosphere, Environmental Microbiology, 9, p383-392.
49. Schäffner, A., Messner, B., Langebartels, C., Sandermann, H., (2002), Genes and enzymes for inplanta phytoremediation of air, water and soil, Acta Biotechnologica, 22, p141-52.
50. Schmitz, H., Hilger, U., Weinder, M., (2000), Assimilation and metabolism of formaldehyde by leaves appear unlikely to be of value for indoor air purification, New Phytologist, 147, p307-315.
51. Shen, Y.S., Ku, Y., (2002), Decomposition of gas-phase trichloroethene by the UV/TiO2 process in the presence of ozone, Chemosphere, 46, p101-107.
52. Shiraishi, F., Toyoda, K., Miyakawa, H., (2005), Decomposition of gaseous formaldehyde in a photocatalytic reactor with a parallel array of light sources-2. Reactor performance, Chemical Engineering Journal, 114, p145-151.
53. Sidheswaran, M.A., Destaillats, H., Sullivan, D.P., Cohna, S., Fisk, W.F., (2012), Energy efficient indoor VOC air cleaning with activated carbon fiber (ACF) filters, Building and Environment, 47, p357-367.
54. Stevens, L., Lanning, J.A., Anderson, L.G., Jacoby, W.A., Chornet, N., (1998), Investigation of the photocatalytic oxidation of low-level carbonyl compounds, Journal of the Air & Waste Management Association, 48, p979-984.
55. Strini, A., Cassese, S., Schiavi, L., (2005), Measurement of benzene, toluene, ethylbenzene and o-xylene gas phase photodegradation by titanium dioxide dispersed in cementitious materials using a mixed flow reactor, Applied Catalysis B-Environmental, 61, p90-97.
56. Sundell, J., (2004), On the history of indoor air quality and health, Indoor Air, 14, p51-58.
57. Tarran, J., Torpy, F., Burchett, M., (2007), Use of living pot-plants to cleanse indoor air-Research Review, Proceedings of Sixth International Conference on Indoor Air Quality, Ventilation & Energy Conservation in Buildings-Sustainable Built Environment, Sendai, Japan, III, p249-256.
58. Tompkins, D.T., Lawnicki, B.J., Zeltner, W.A., Anderson, M.A., (2005), Evaluation of photocatalysis for gas-phase air cleaning-Part 1: process, technical and sizing considerations, ASHRAE Transactions, 111, p60-64.
59. Tucker, W.C., (2001), Volatile organic compounds in indoor air quality handbook, J.D. Spengler, J.M. Samet, and J.F. McCarthy, e.d., McGraw-Hill, New York.
60. USEPA, (2002), Child-specific Exposure Factors Handbook, EPA/600/P-00/002B, U.S. Environmental Protection Agency, National Center for Environmental Assessment, Washington, DC.
61. Wang, S., Ang, H.M., Tade, M.O., (2007), Volatile organic compounds in indoor environment and photocatalytic oxidation: State of the art, Environment International, 33(5), p694-705.
62. Wolkoff, P., (2003), Trends in Europe to reduce the indoor air pollution of VOCs, Indoor Air, 13, p5-11.
63. Wolkoff, P., Clausen, P.A., Jensen, B., Nielsen, G.D., Wilkins, C.K., (1997), Are we measuring the relevant indoor pollutants?, Indoor Air, 7, p92-106.
64. Wolkoff, P., Nielsen, G.D., (2001), Organic compounds in indoor air their relevance for perceived indoor air quality?, Atmospheric Environment, 35, p4407-4417.
65. Wood, R.A., Burchett, M.A., Alquezar, R., Orwell, R.L., Tarran, J., Torpy, F., (2006), The potted-plant microcosm substantially reduces indoor air VOC pollution: I. Office field-study, Water Air Soil Pollut, 175, p163-180.
66. Wood, R.A., Orwell, R.L., Burchett, M.D., Tarran, J., Torpy, F., (2003), Pottedplant/growth media interactions and capacities for removal of volatiles from indoor air, In Proceedings of Healthy Buildings 2003, 7th International Healthy Buildings Conference (Tham, K.W., Sekhar, C. and Cheong, D. Eds.), National University of Singapore.
67. Wolverton, B.C., Johnson, A., Bounds, K., (1989), Interior landscape plants for indoor air pollution abatement, National Aeronautics and Space Administration, p1-22.
68. Wolverton, B.C., McDonald, R.C., Watkins, Jr. E.A., (1984), Foliage plants for removing indoor air pollutants from energy-efficient homes, Economic Botany, 38, p224-228.
69. Wolverton, B.C., Wolverton, J.D., (1993), Plants and soil microorganisms: removal of formaldehyde, xylene, and ammonia from the indoor environment, Journal of the Mississippi Academy of Sciences, 38(2), p11-15.
70. Yang, D.S., Pennisi, S.V., Son, Ki-C, Kays, S.J., (2009), Screening indoor plants for volatile organic pollutant removal efficiency, HortScience, 44, p1377-1381.
71. Yao, M., Zhang, Q., Hand, D.W., Perram, D.L., Taylor, R., (2009a), Investigation of the treatability of the primary indoor volatile organic compounds on activated carbon fiber cloths at typical indoor concentrations, Journal of the Air & Waste Management Association, 59(7), p882-890.
72. Yao, M., Zhang, Q., Hand, D.W., Perram, D.L., Taylor, R., (2009b), Adsorption and regeneration on activated carbon fiber cloth for volatile organic compounds at indoor concentration levels, Journal of the Air & Waste Management Association, 59(1), p31-66.
73. Yu, C., Crump, D., (1998), A review of the emission of VOCs from polymeric materials used in buildings, Building and Environment, 33, p357-374.
74. Yu, Q.L., Brouwers, H.J.H., (2009), Indoor air purification using heterogeneous photocatalytic oxidation. Part I: Experimental study, Applied Catalysis B: Environmental, 92, p454-461.
75. Yu, Q.L., Brouwers, H.J.H., Ballari, M.M., (2009), Experimental study and modeling of the photocatalytic oxidation of NO in indoor conditions, 3rd international symposium on nanotechnology in construction, Prage, Czech Republic.
76. Zhao, J., Yang, X., (2003), Photocatalytic oxidation for indoor air purification: a literature review, Building and Environment, 38, p645-654.